The OAC5A output module is used for controlling or switching AC loads of 24-280 VAC. Each module provides up to 4000 volts (transient) of optical isolation between the field devices and the control logic. This module is equivalent to a single pole, single throw, normally open contact (FORM A, SPST-NO, Make). All AC output modules feature zero voltage turn-on and zero current turn-off.
Typical uses and applications for AC output modules include switching the following loads:
- Relays
- Solenoids
- Motor starters
- Heaters
- Lamps or indicators
|
One Cycle Surge |
80 amps peak |
|
Peak Repetitive Voltage |
500 Volts |
|
Operating Ambient Temperature |
-30 to 70 °C |
|
Isolation, Input-to-Output (Transient) |
4,000 Vrms |
|
Minimum Load Current |
20 milliamps |
|
Operating Frequency |
25–65 Hz |
|
Turn-on Time |
1/2 cycle maximum-zero voltage |
|
Turn-off Time |
1/2 cycle maximum-zero current |
|
DV/DT – Off-State |
200 volts/microseconds |
|
DV/DT – Commutating |
Snubbed for rated 0.5 power factor load |
|
Output Voltage Drop Maximum Peak |
1.6 volts |
|
Off-State Leakage |
5 milliamps rms 2.5 milliamps rms for OAC5A OAC15A, and OAC24A @120 VAC |
Module Specifications
|
|
Units |
OAC5A5 |
|
Line Voltage – Nominal |
VAC |
120/240 |
|
Operating Voltage Range |
VAC |
24–280 |
|
Current Rating |
amps amps |
3 2 |
|
UL Motor Load Rating |
amps |
1.5 |
|
Logic Voltage – Nominal |
VDC |
5 |
|
Logic Voltage Range (Vcc)2 |
VDC |
2.5–8 |
|
Logic Pickup Voltage1 |
VDC |
2.5 |
|
Logic Dropout Voltage |
VDC |
1 |
|
Logic Input Current-@ Normal Logic |
mA |
12 |
|
Control Resistance |
Ohms |
220 |